Multipair Individual/overall Screen with Armor and Lead Sheath

 

Application :

  • These cable can be used in cable tray or conduit to connect different types of thermocouple in industrial process controls, refineries, oil and gas plant. Excellent protection against corrosion, humidity and poor vibration resistance.

Specification :

  • Conductor Solid
    Type applicable KX, EX, JX, TX, NX, KCA, KCB, RCA, RCB, SCA, RCB, BC
    Insulation PVC, PE, XLPE or LSZH thermoplastic material
    Individual screen 24 μm aluminium / PETP tape over solid tinned copper drain wire, 0.6 mm
    Wrapping At least 1 layer of plastic tape
    Overall screen 24 μm aluminium / PETP tape over 7-stranded tinned copper drain wire, 0.5 mm²
    Bedding PE, PVC or LSZH thermoplastic material
    Lead sheath Lead alloy
    Inner sheath PVC or LSZH thermoplastic material
    Armor Galvanized round steel wires
    Outer sheath PVC or LSZH thermoplastic material
    Color code According to IEC 60584-3
    Flame retardancy IEC 60332-1
    Flame propagation IEC 60332 cat. C
    Temperature range -30°C up to 70°C during operation. -5°C up to 50°C during installation
  •  

      KCB IS/OS & armored with lead sheath

0.5 mm² :

  • No. of Pairs Insulation Thickness (mm) Bedding Thickness (mm) Lead Sheath Thickness (mm) Inner Sheath Thickness (mm) Diameter of Armor Wire (mm) Outer Sheath Thickness (mm) Nominal O.D. (mm) Weight* (kg/km)
    2 0.4 0.9 1.1 0.8 0.9 1.4 17.3 892
    4 0.4 1.1 1.1 0.8 0.9 1.4 18.9 1078
    6 0.4 1.2 1.1 0.8 0.9 1.5 21.2 1309
    8 0.4 1.2 1.2 0.8 0.9 1.5 22.3 1491
    10 0.4 1.2 1.2 0.8 1.25 1.6 25.4 1912
    12 0.4 1.2 1.2 0.9 1.25 1.6 25.8 2000
    16 0.4 1.3 1.3 0.9 1.25 1.7 28.2 2383
    20 0.4 1.3 1.3 0.9 1.25 1.7 29.5 2610
    24 0.4 1.3 1.4 1.0 1.25 1.8 32.6 3087

0.8 mm² :

  • No. of Pairs Insulation Thickness (mm) Bedding Thickness (mm) Lead Sheath Thickness (mm) Inner Sheath Thickness (mm) Diameter of Armor Wire (mm) Outer Sheath Thickness (mm) Nominal O.D. (mm) Weight* (kg/km)
    2 0.4 0.9 1.1 0.8 0.9 1.4 18.0 970
    4 0.4 1.1 1.1 0.8 0.9 1.5 20.2 1204
    6 0.4 1.2 1.1 0.8 0.9 1.5 22.3 1451
    8 0.4 1.2 1.2 0.8 0.9 1.6 24.6 1848
    10 0.4 1.2 1.2 0.9 1.25 1.6 26.9 2137
    12 0.4 1.3 1.3 0.9 1.25 1.7 28.2 2383
    16 0.4 1.3 1.3 0.9 1.25 1.7 30.0 2690
    20 0.4 1.3 1.4 1.0 1.25 1.8 32.1 3092
    24 0.4 1.5 1.4 1.0 1.25 1.8 35.2 3581

1.0 mm² :

  • No. of Pairs Insulation Thickness (mm) Bedding Thickness (mm) Lead Sheath Thickness (mm) Inner Sheath Thickness (mm) Diameter of Armor Wire (mm) Outer Sheath Thickness (mm) Nominal O.D. (mm) Weight* (kg/km)
    2 0.4 1.1 1.1 0.8 0.9 1.4 18.4 1011
    4 0.4 1.1 1.1 0.8 0.9 1.5 20.2 1204
    6 0.4 1.2 1.2 0.9 0.9 1.6 23.6 1691
    8 0.4 1.2 1.2 0.9 1.25 1.6 24.6 1848
    10 0.4 1.2 1.3 0.9 1.25 1.7 27.5 2244
    12 0.4 1.3 1.3 0.9 1.25 1.7 28.2 2383
    16 0.4 1.3 1.4 1.0 1.25 1.7 30.2 2781
    20 0.4 1.5 1.4 1.1 1.25 1.8 32.5 3154
    24 0.4 1.5 1.5 1.2 1.6 1.9 36.5 3982

1.3 mm² :

  • No. of Pairs Insulation Thickness (mm) Bedding Thickness (mm) Lead Sheath Thickness (mm) Inner Sheath Thickness (mm) Diameter of Armor Wire (mm) Outer Sheath Thickness (mm) Nominal O.D. (mm) Weight* (kg/km)
    2 0.4 1.1 1.1 0.8 0.9 1.5 19.8 1140
    4 0.4 1.2 1.2 0.9 0.9 1.5 22.5 1588
    6 0.4 1.2 1.2 1.0 1.25 1.6 25.1 1915
    8 0.4 1.2 1.3 1.1 1.25 1.6 26.4 2190
    10 0.4 1.3 1.3 1.1 1.25 1.7 29.7 2606
    12 0.4 1.3 1.4 1.1 1.25 1.7 30.5 2843
    16 0.4 1.3 1.4 1.2 1.25 1.8 32.5 3235
    20 0.4 1.5 1.5 1.2 1.25 1.9 35.2 3797
    24 0.4 1.5 1.5 1.2 1.6 1.9 39.5 4653

1.5 mm² :

  • No. of Pairs Insulation Thickness (mm) Bedding Thickness (mm) Lead Sheath Thickness (mm) Inner Sheath Thickness (mm) Diameter of Armor Wire (mm) Outer Sheath Thickness (mm) Nominal O.D. (mm) Weight* (kg/km)
    2 0.5 1.1 1.2 0.9 0.9 1.5 21.1 1303
    4 0.5 1.2 1.2 1.0 0.9 1.5 23.7 1741
    6 0.5 1.2 1.3 1.1 1.25 1.6 26.9 2193
    8 0.5 1.3 1.3 1.1 1.25 1.7 28.7 2481
    10 0.5 1.3 1.4 1.2 1.25 1.7 31.9 2995
    12 0.5 1.3 1.4 1.2 1.25 1.7 32.6 3164
    16 0.5 1.5 1.5 1.3 1.25 1.9 36.3 3863
    20 0.5 1.5 1.6 1.3 1.6 1.9 39.2 4686
    24 0.5 1.7 1.6 1.3 1.6 2.0 43.6 5471
  • *The number here is just approx. weight. It changes according to the insulation material and the conductor used in different type of extension cable and compensating cable.